The generator’s battery doesn’t have enough electrical power to reliably start or run the system.
Symptoms
- Won’t start
- Clicking sound when attempting to start
- Low voltage or charging alarms
- Intermittent startup failure
Causes
- Battery aging
- Charging system failure
- Loose/corroded battery terminals
- Performance drop due to cold weather
Troubleshooting steps
- Check voltage, should be 12.6 volts or higher
- Inspect battery connections: look for loose connections or corrosion built up on terminals
- Test charger output: depending on temperature 13.5-14.6 VDC
- Replace battery if needed
Fixes
- Battery replacement
- Cleaning terminals
- Replace charger (controller)