If your Generac generator won’t start, the issue is usually related to battery failure, fuel delivery, or a controller fault. This guide walks through step-by-step checks used in real troubleshooting scenarios.
Symptoms
- Generator does not start during outage
- Clicking noise but no crank
- Display shows alarm or error code
- Dead control panel or no response
- Starts then shuts down quickly
Common Causes
- Weak or dead battery (most common)
- Fuel supply issue (LP/NG or vapor lock)
- Controller set to OFF position
- Controller lockout condition
Troubleshooting Steps
Step 1: Check the battery
- Measure voltage if possible
- If below 12.4 volts, charger may not be working
- If above 12.4 volts charger may be working but battery may be too weak/lacking cranking amps
- Check battery terminals and cables for corrosion and tightness
Step 2: Check for display or error codes
- Note any fault codes shown
- See Generac error codes guide section
Step 3: Check fuel supply
- Ensure gas shut off valve is open
- Confirm LP tank or NG supply is active
Step 4: Attempt restart
- Press OFF the ENTER buttons to clear alarms on EVO (Guardian) units
- Hold OFF button for 3 seconds to clear alarms on NextGen units
- Attempt to start unit in MANUAL or put into AUTO mode
- If it still fails, move to electrical or controller diagnostics
Common fixes
- Replace battery if weak
- Reset breaker on generator
- Clear fault code and retry start cycle
- Restore fuel supply pressure
- Perform hard reset of controller
Quick tip!
If the controller buttons are unresponsive or you are not able to navigate through the menus on the display screen, the controller may just need a reset.
How to “hard reset” the controller
1. Pull the 7.5 Amp fuse from the controller. (this kills battery power to the controller)

2. Disconnect the T1 line. (This is the 120 VAC source to the controller)
The T1 voltage can be disconnected in two ways:
First way – Disconnect the white two wire molex connector. Follow the white sheathed cable that comes out of the top corner of the controller down to the connector. See Image A.
Second way – Pull the fuse for the T1 line in the transfer switch. See Image B.


3. After the 7.5 Amp fuse has been pulled from the controller and the T1 line has been disconnected there should be no lights or display on the controller. To complete the hard reset, put the fuse back in the controller and then reconnect the T1 line. The controller should restart and prompt you to go through the Install Wizard.
When to call a technician
If the generator continues to fail after basic checks or displays persistent fault codes, a certified Generac technician should perform advanced diagnostics.
Related Troubleshooting Guides
- Generac Error Code 1505 – Meaning and Troubleshooting Guide
- Generac Error Code 1100 – Overcrank Meaning and Troubleshooting Guide
- Generac Error Code 1902 – Undervoltage Meaning and Troubleshooting Guide
- Generac Error Code 2099 – Wiring Error Meaning and Troubleshooting Guide
- Generac Low Battery Voltage Troubleshooting
- Generac Battery Charger Failure – Causes and Fixes
- Generac Generator Starts Then Shuts Down – Troubleshooting Guide
- Generac Generator Clicking But Not Starting – Causes and Fixes
- Generac Generator Cranks But Won’t Start – Causes and Fixes