If your generator cranks normally but never starts, the starter motor and battery are likely doing their job. The problem is usually related to fuel delivery, ignition, air flow, or a safety condition preventing the engine from running.
The good news is that hearing the engine crank eliminates several possible causes and narrows the troubleshooting process.
What Does “Cranks But Won’t Start” Mean?
Cranking means the starter motor is rotating the engine, but the engine never begins running on its own.
You may hear the engine turning over for several seconds before it stops without ever starting.
Most Common Causes
1. Low fuel pressure or fuel delivery issue
If it’s a new or newer install:
- Verify correct fuel pressure. 5″ WC to 7″ WC for natural gas and 10″ WC to 12″ WC for liquid propane.
- Fuel pressure at the top port of the internal demand regulator must be within range at all times.
- Verify fuel shutoff valve is open.
- Verify fuel selector is set to the correct fuel type as well as on the controller.
- Check fuel lines from demand regulator to mixer/throttle for sharp bends or kinks.
2. Weak spark plug or ignition problem
A worn spark plug may prevent ignition even though the engine cranks normally.
Inspect for:
- Correct spark plug type per owner’s manual
- incorrect gap
- carbon buildup
- excessive wear
- damaged electrode
Replace the spark plug if it shows signs of wear.
3. Dirty air filter
An excessively dirty air filter can reduce airflow enough to affect starting.
Check For:
- Dirt buildup
- oil contamination
- Rodent nesting material
- Some air filters from factory have an excessive amount of fire retardant material that can impede air flow
Replace the filter if necessary.
4. Mixer/carburetor issues
When generator is cranking:
- Inspect throttle linkage for movement.
- Throttle linkage should be moving, indicating throttle plates are sweeping open and shut
- If no movement is seen, this can point to an issue with the stepper motor.
Step-by-Step Troubleshooting
Step 1
Verify generator is getting fuel. Make sure fuel shut off valve is open. Is the fuel solenoid on the demand regulator clicking and opening?
Step 2
Open airbox and inspect or try replacing the air filter. Try starting unit with air filter removed.
Step 3
Inspect throttle linkage for movement when cranking engine. If there is no movement, this is your issue.
Step 4
Check for strong ignition spark. Bright blue or white/purple indicate strong spark. Replace spark plug if it is fouled and ensure gap is correct.
When to Call a Technician
- Fuel, spark plug, battery, and air filter all check out.
- Diagnostic fault codes appear during the start sequence.
- A technician can perform ignition, fuel pressure, and compression testing to identify less common failures.