Error code 1902 Undervoltage means the generator is not producing sufficient output voltage. It is a shutdown fault designed to protect connected appliances and the generator itself.
Symptoms
- Low or fluctuating voltage at the load center/breaker (e.g., below 220-240V).
- Lights dimming or appliances not running properly before shutdown.
- Generator starts and display shows “WARMING UP” for 4 minutes before shutting down.
Common Causes
- Worn brushes, slip rings, rotor or stator issues.
- Loose or missing hardware on the stator terminal block.
- Generator is overloaded.
- Engine not reaching or maintaining proper RPM.
Troubleshooting Steps
Step 1. Check output voltage
- Clear the fault by pressing the OFF button, then the ENTER button.
- Attempt to run in MANUAL mode and monitor voltage output at the breaker with a multimeter.
Step 2. Determine what the output voltage you are measuring means
- 0V or near zero (residual voltage) the issue likely stems from low field boost voltage, worn or damaged slip ring brushes, grooved or damaged slip rings, or a short in the rotor.
- 90-190V (give or take 10%) Low field boost voltage, open or shorted winding on the stator.
- 300V or greater – The controller/AVR is not seeing or only seeing partial output voltage, so it is trying to compensate by boosting output.
- 240V (approx.) This is normal output voltage. Check output voltage when the generator is under load.