Error Code 1300 on a Generac home standby generator means the controller has detected low oil pressure and has shut the unit down to protect the engine from damage.
Symptoms
- Generator starts but shuts down quickly (usually within seconds to a minute)
- Red LED illuminated
- No power to the house during an outage
- May occur during weekly exercise or when load is applied
Common Causes
- Low oil level (most common — oil consumption, leaks, or missed maintenance)
- Faulty oil pressure sensor/switch (very common failure on air-cooled units)
- Oil leaks (crankcase gasket, sensor itself, drain plug, etc.)
- Internal engine issues (worn bearings, oil pump failure – rare but serious)
- Generator has been running for extended periods of time, nonstop.
Troubleshooting Steps
1. Check the oil level
- Keep the generator OFF and allow the engine to cool.
- Pull the dipstick, wipe it clean, reinsert fully, and pull again.

- Oil should be between the lower and upper marks.

- If low, add the correct oil in small increments and recheck.
2. Inspect for visible oil leaks
- Check around the oil drain plug, oil filter, oil cooler lines and oil pressure sensor.

- Look underneath the unit for fresh oil spots.
- Pay special attention to the oil pressure switch. These commonly leak when failing.
3. Perform an Oil Change (Recommended if Due)
If the oil is old, dirty, or you’re unsure when it was last changed:
- Change the oil and oil filter.
- Use only Generac approved or manufacturer-recommended oil.
4. Test the oil pressure sensor
- Locate the oil pressure switch (usually near the oil filter housing).

- If the switch says NC (Normally Closed) disconnect the wires and leave them separated to bypass the switch.
- If the switch says NO (Normally Open) disconnect the wires and jump them together to bypass the switch.
- Run the generator in MANUAL mode.
- If it runs without shutting down, the sensor is likely bad. Replace it.
- If it still shuts off for 1300 code, there may be an issue with the wiring or the controller.

If after replacing the low oil pressure sensor, unit still faults for 1300, this could indicate the oil pump is not building enough oil pressure!
When To Call A Technician
- You’ve bypassed the oil pressure switch and unit is still shutting down.
- You cannot find the source of an oil leak or it appears to be coming from the engine block.
- Suspected internal engine damage (metal in oil, knocking sounds, etc.)