Where is the battery charger?
On older Generac home standby models the charger is sometimes located in the transfer switch panel or within the control panel area on the generator as a separate module. However, on newer units with Nexus and Evolution controllers, the battery charger is built into the controller.
What Does Battery Charger Failure Mean?
- The generator’s onboard battery charger keeps the starting battery fully charged when utility power is available.
- If the charger stops working, the battery slowly loses charge until the generator can no longer crank and start the generator.
- This issue often appears alongside alarms such as: Low Battery, Battery Problem, Charger Warning and Charger Missing AC.
Common Symptoms
- Battery Charger Failure message on the display
- Low Battery Voltage warning
- Dead battery after sitting
- Generator won’t crank during an outage
- Battery repeatedly needs to be charged
- Weak or slow cranking
What Causes a Battery Charger Failure?
| Cause | Fix | Likelihood |
|---|---|---|
| Utility power lost to charger | Verify 120VAC on T1 wire to charger | High |
| Tripped breaker | Check main breaker in transfer switch panel | Low |
| Loose battery connections | Inspect, tighten and clean connections if necessary | High |
| Blown fuse | If the T1 fuse in the transfer switch is blown, charger will not receive the 120VAC from utility it needs to charge the battery | Medium |
| Failed battery | Old or faulty battery will not take a charge | High |
| Damaged wiring | Look for burnt/damaged wiring. Replace as needed. | Low |
How to Fix It
Step 1: Verify charger is receiving power
The charger requires 120 VAC from utility when the generator is not running or when running but utility power is still present. Such as during it’s exercise cycle or if running the unit in manual.
- Quickest way to test – Pull the 7.5 amp fuse from the front of the controller.
- If the controller stays illuminated/lights stay on, it is receiving AC voltage required to charge the battery.
- If by pulling the fuse the controller goes dark/no lights, controller is likely not receiving AC voltage.
- Check T1 wire fuse in the transfer switch panel. If fuse is blown, no AC voltage will make it to charger.
- Replace fuse as necessary.
Step 2: Inspect battery connections
- Clean corrosion.
- Tighten terminals.
- Look for damaged cables.
Step 3: Test the Battery
- A battery that won’t hold a charge can actually cause a charger fault.
- A Charger Warning can appear if the charger is unable to raise the battery voltage above 12.5V.
- Test the battery with a battery tester and replace if necessary.
Step 4: Check Charger Output
For Guardian series generators, the charger operates at one of three battery charging voltage levels depending on ambient temperature:
- 13.5 V at high temp
- 14.1 V at normal temp
- 14.6 V at low temp
A quick test is to turn off fuel source so the generator does not start and crank the engine. This will lower the battery voltage which should then in turn cause the charger to turn on and charge the battery. Using a multimeter, if you are not seeing battery voltage climb back up into the specified ranges listed above, the charger is likely not working.
Step 6: Replace the Battery Charger (if necessary)
Replacing the charger will require replacement of the generator controller (the module with the display and buttons). Unless it’s a much older unit that has a separate battery charger not built into the controller.